The modular switch disconnectors of SD series, allow the breaking and the disconnecting on load of equipment on low voltage at nominal current from 16 to 125A.
USE
The switch disconnectors of SD series are commonly used for the following purposes:
• main switch
• switch for motors
• safety switch
• disconnector
GENERAL CHARACTERISTICS
• high breaking capacity (AC 22 A - AC 23 A)
• double break contacts
• high electrical and mechanical endurance
• resistant to damp heat
• IP20 degree of protection
• modular execution, basic mounting on 35 mm DIN rail and by screws, modular window 45mm.
RANGE COMPOSITION
• SD1 three poles for 16-25-32-40-63A
• SD2 three poles for 63-80-100-125A
ADDITIONAL POLES
• Fourth switched pole, solid neutral and earth pole.
OPERATING MECHANISM
• Black (standard execution) or emergency direct handle padlockable in 0 position.
• Handle with and without door interlock handle, black or emergency handle padlockable with up to three padlocks in 0 position.
• IP 65 degree of protection.
• By toggle padlockable in 0 position (switch SD2).
• Wide range of accessories.
CONFORMITY TO STANDARDS
• IEC 60947/1-3
• CEI EN 60947/1-3
• UL 508
CERTIFICATES AND APPROVALS
• CESI
Characteristics
SD1
16A
25A
32A
40A
63A
Rated insulation voltage
Ui
(V)
800
800
800
800
800
Inpulse with listand voltage
Uimp
(kV)
8
8
8
8
8
Rated thermal current at 40°C
Ith/Ithe
(A)
16
25
32
40
63
Rated operational current le
AC-21A
415V
(A)
16
25
32
40
63
500V
(A)
16
25
32
40
63
690V
(A)
16
25
32
40
63
AC-22A
415V
(A)
16
25
32
40
63
500V
(A)
16
25
32
40
63
690V
(A)
16
25
32
40
40
AC-23A
415V
(A)
16
25
32
40
40
500V
(A)
16
25
32
40
40
690V
(A)
16
25
25
25
25
Rated making capacity at 415V AC23
(A)
160
250
320
400
400
Rated breaking capacity at 415V AC23
(A)
128
200
256
320
320
Rated operational power AC23
415V
(kW)
7,5
11
14
15
15
500V
(kW)
7,5
11
14
15
18,5
690V
(kW)
7,5
11
14
15
18,5
Short-circuit withstand current 1 sec
(400V)
(kA)
1,1
1,1
1,1
1,1
1,1
Rated fuses short circuit current
Back up fuse gG
(A)
16
25
32
40
63
R.M.S. value
(kA)
50
50
50
50
20
Peak value
(kA)
3,8
4,5
5
5,7
5,7
Mechanical endurance
n.
50000
50000
50000
50000
50000
Electrical endurance
n.
3000
3000
3000
3000
3000
Power loss per pole
W
0,05
0,12
0,32
0,32
0,8
Cable selection
mmq
16
16
16
16
16-25
Max terminal torque
Nm
2
2
2
2
2
Operation torque
Nm
1,6
1,6
1,6
1,6
1,6
Auxiliary contacts AC 15/415V
A
3
3
3
3
3
Net weight 3 poles
Kg.
0,13
0,13
0,13
0,13
0,13
Net weight 4 poles
Kg.
0,16
0,16
0,16
0,16
0,16
SD1 16÷63A
SD2 63÷125A
Serie
SD1
Rated current
16A
25A
32A
40A
63A
Direct handle standard 3 poles switch
19200
19201
19202
19203
19204
Direct emergency handle 3 poles switch
19210
19211
19212
19213
19214
Serie
SD2
Rated current
63A
80A
100A
125A
Direct handle standard 3 poles switch
19205
19206
19207
19208
Direct emergency handle 3 poles switch
19215
19216
19217
19218
Net weight 3 poles
19205LE
19206LE
19207LE
19208LE
ACCESSORIES
SD1
16÷63A
SD2
63÷125A
ACCESSORI
SD1
16÷63A
SD2
63÷125A
Emergency door interlock handle
19401
Solid neutral
19419
19420
Door interlock handle
19400
6-8 poles switches SD1-SD2 attachement kit from 16÷125A shaft max 200 mm
19440
Shaft 100,200,300mm (*)
19535
Auxiliary contacts 1NO+1NC screw terminals (**)
19423
19429
Door interlock handle for change-over (1-0-2)
19402
Auxiliary contacts 1NO+1NC Faston terminal (**)
19428
19430
Fourth pole
19414
19418
3 poles terminals cover kit
19424
19425
Hearting neutral
19421
19422
4th pole terminal cover kit
19426
19427
(*) To be eployed with SD2 change-over and with 6/8 poles switch shaft, 200 mm max width.
(**) Rated current 10A 400V - 16A 250V ac - Break before main contacts.
All the accessories are suitable to be employed with switches and change-overs of SD series, except for specific indications.